Sample Pre-Delivery Inspection Report
This interactive preview showcases the structured format, photographic defect catalog, and builder rectification checklist delivered within 24–48 hours of your home inspection.
PDI Audit — Pride Platinum, Wakad, Pune
Swipeable Defect Photo Reel
Touch or swipe across defect evidence captured during the on-site walkthrough. Tap any image to expand.
Documented Snag List with Photographic Evidence
Reverse Polarity on 16A Air Conditioner Socket
Socket test instrument detected Live and Neutral terminals wired in reverse. Potential electrical fire and component burnout hazard for split AC unit.
8 Hollow Vitrified Floor Tiles (Void Under Surface)
Acoustic tap hammer examination revealed extensive hollow sounds across an 8-tile cluster near balcony sliding door. Caused by insufficient mortar adhesive spread.
Reverse Floor Slope Causing Water Puddle Around Commode
Water flow test demonstrated stagnant puddle accumulating behind wall-hung WC rather than draining into nahani floor trap. 6mm slope deviation recorded.
Active Seepage at Stainless Steel Sink Bottle Trap Flexi-Pipe
Continuous water discharge under kitchen counter during sink drainage test. Unsealed rubber washer at PVC trap joint.
Missing Silicone Weather Sealant on Outer Aluminium Frame
Visible 4mm gap between powder-coated aluminium window frame and external plaster lintel. High risk of rainwater ingress during Pune monsoons.